PLC S7 Driver

PLC S7 Driver

dc3-driver-plcs7 connects Siemens S7 series PLCs to IoT DC3: acting as an S7 client, it connects over TCP to one or more PLCs, periodically reads values according to the data block number and offset configured on each Point, and supports writing values back. After this page you can fill in the right host / plcType / dbNum attributes on a device, turn a DB variable into a readable and writable Point, and diagnose the most common cannot-connect, wrong-value, and write-failure problems.

Protocol background

S7 (also called S7comm / ISO-on-TCP) is the proprietary Ethernet protocol used by Siemens PLCs ( S7-200/300/400/1200/1500, S7-200 Smart, and SINUMERIK CNC systems). It runs on top of ISO 8073 COTP, encapsulated in TCP on the standard port 102, and is used to read and write the PLC's internal memory areas directly — especially the Data Blocks (DB) that engineers define in STEP 7 / TIA Portal.

In terms of communication model, S7 is a classic master/slave, request-response protocol: this driver acts as the master (client), actively opening connections and sending read/write requests to each PLC in turn, while the PLC responds passively and never pushes on its own. Addressing uses the numeric form "DB number + byte offset (+ bit offset)", aligned by engineering convention — which means that before onboarding you must look up, from the PLC program, which DB and which byte each variable lives at.

In the four-layer IoT architecture, S7 sits on the wired-industrial side of the network layer: it solves the last mile of "how data inside a PLC gets read by an external system over Ethernet". For the communication models, addressing schemes, and byte-order trade-offs of industrial bus protocols, see Industrial Bus and Protocols.

flowchart LR
  subgraph DC3["IoT DC3"]
    Drv["dc3-driver-plcs7<br/>S7 client (master)"]
  end
  Drv -->|"TCP:102 read/write request<br/>address DB{n}.{byte}[.{bit}]"| PLC1["S7-1200 PLC<br/>host=192.168.0.20"]
  Drv -->|"TCP:102"| PLC2["S7-1500 PLC<br/>host=192.168.0.21"]
  PLC1 -.->|"reply DB bytes"| Drv
  PLC2 -.-> Drv

A single driver process can connect to multiple PLCs; connections are reused per deviceId, and each PLC is distinguished by the host and plcType on its own Device.

Attribute configuration

S7 has no separate "write-command attribute" (application.yml has no command-attribute). Addressing information splits into two layers: driver attributes locate "which PLC to connect to", and point attributes locate "which variable inside the PLC to read". The fields, types, and defaults in both tables below come from the driver's application.yml.

Driver attributes (device-level driver-attribute)

When onboarding an S7 PLC device, fill in these attributes on the Device. host and port together determine the connection target, while plcType selects which S7 addressing scheme the driver uses to resolve DB addresses and byte order.

Attribute code Type Default Description
Host host STRING 192.168.0.20 PLC IP address
Port port INT 102 S7 TCP port, standard 102
PLC Type plcType STRING S1200 PLC model, values below

::: tip plcType decides how addresses are resolved Different S7 PLC models differ in DB addressing detail and data layout; plcType selects the matching S7 addressing scheme. Valid values come from the underlying EPlcType enum: S200 / S200_SMART / S300 / S400 / S1200 / S1500 / SINUMERIK_828D. Typical mapping: use S1200 for S7-1200, S1500 for S7-1500, and S200_SMART for S7-200 Smart. If the value is wrong or outside the enum, the driver logs a warning and falls back to S1200. :::

Point attributes (point-attribute)

Each Point locates a single variable inside a PLC data block. The driver assembles these three items into an S7 address string and hands it to the underlying library: a non-boolean Point becomes DB{dbNum}.{byteOffset}, and only when the Point is boolean and bitOffset > 0 does it become DB{dbNum}.{byteOffset}.{bitOffset}.

Attribute code Type Default Description
DB Number dbNum INT 0 Data block number, counted from 0
Byte Offset byteOffset INT 0 Byte offset within the data block
Bit Offset bitOffset INT 0 Bit offset within the byte (only for boolean Points when > 0)

::: tip The Point type decides how many bytes are read Read/write width is derived from the Point's data type (the pointTypeFlag of the Point) starting at byteOffset, with no extra configuration: BOOLEAN takes one bit, BYTE 1 byte, SHORT 2 bytes, INT/FLOAT 4 bytes, LONG/DOUBLE 8 bytes, STRING reads a string. So the same DB offset configured as different Point types reads values of different widths. :::

::: warning bitOffset only applies to boolean Points and only when non-zero The driver uses bit addressing (an address with a third .bit segment) only when the type is boolean and bitOffset > 0. In every other case — non-boolean types, or boolean with bitOffset=0 — it addresses at byte level as DB{dbNum}.{byteOffset}. Setting bitOffset on a float Point causes no error and has no effect; to move across bytes change byteOffset, do not use bitOffset to "skip" bytes. :::

Writing a Point reuses that Point's own attributes (dbNum / byteOffset / bitOffset) to locate the address, and the write width is determined by the value type carried by the command. Once a writable Point has these three items configured, it can be both read and written — no extra write-command configuration is needed.

Troubleshooting

When onboarding S7, these are the most common traps; most are PLC-side settings rather than driver problems.

::: danger The PLC side must allow PUT/GET access S7-1200/1500 block external PUT/GET communication by default — this is the most common cause of onboarding failure. In the CPU properties in TIA Portal you must check "Permit access with PUT/GET communication from remote partner". Otherwise the TCP connection establishes but every read/write is rejected by the PLC. :::

::: warning The DB must have "Optimized block access" turned off If the data block being accessed has "Optimized block access" enabled, variables no longer have fixed byte offsets inside the DB, so locating by byteOffset reads wrong values or fails. In TIA Portal, select the DB → Properties → uncheck "Optimized block access"; after compiling and downloading, the offset addresses become stable and usable. :::

  • Port 102 unreachable: S7 runs over TCP 102; confirm the PLC IP (host) is reachable, the firewall is not blocking it, and port has not been changed to a non-standard value. Verify the link with ping and telnet <host> 102 before blaming the driver.
  • Wrong plcType breaks address resolution: a wrong model falls back to S1200, which can read misaligned values on S7-300/400/1500. The log line Unknown plcType ... fallback to S1200 means the value is outside the enum — correct it per the table above.
  • Values come back wrong (byte order / offset): first confirm the DB has optimized block access turned off and that dbNum and byteOffset map one-to-one to the variable address in the PLC program; then confirm the Point's pointTypeFlag matches the PLC variable's type width (e.g. PLC Real → FLOAT, DInt → INT).
  • Device stays offline / reconnects frequently: when a read or write throws, the driver invalidates that connection (invalidateConnection) and rebuilds it on the next access. Repeated reconnects usually mean PLC-side rejection, network jitter, or an overloaded PLC; pinpoint with the Driver connection failed / read failed lines in the driver log. For the online-status and lease-timeout mechanism see Device.

How it lands in IoT DC3

  • dc3.driver.code: PlcS7Driver (driver name PLC S7 Driver, type DRIVER_CLIENT). This is a stable routing identifier — do not change it casually.
  • Read: supported. Default collection cron 0/30 * * * * ? (one read round every 30 seconds); each Point is read by address and wrapped into a PointValue.
  • Write: supported. Reuses point attributes to locate the address and writes back to the PLC by the command value type.
  • Subscribe / report: not provided. S7 is a master/slave polling model and the driver does not listen for PLC-initiated pushes — consistent with "S7: read ✓ / write ✓ / subscribe —" in the driver capability matrix.
  • Health check: device health check defaults to cron 0/15 * * * * ?, lease timeout 45 seconds.

::: info Implementation status: available read() / write() / initial() / event() / validate() in PlcS7DriverCustomServiceImpl are all fully implemented, backed by the iot-communication (S7PLC) library, with auto-reconnect enabled, connections reused per deviceId, and a ReentrantLock serializing reads/writes. This is a working driver, not a skeleton. :::

Minimal onboarding example: onboard an S7-1200 at IP 192.168.0.20:102 and read a 32-bit float at offset 0 in DB1:

  1. Create a Device using PLC S7 Driver, and set the driver attributes host=192.168.0.20, port=102, plcType=S1200.
  2. Add a temperature Point (pointTypeFlag=FLOAT) to the Profile bound to the device, and set the point attributes dbNum=1, byteOffset=0, bitOffset=0.
  3. Confirm the PLC has PUT/GET enabled and that DB's optimized block access is off, start the driver, and within 30 seconds you will see the collected value in PointValue.