Modbus RTU Driver
dc3-driver-modbus-rtu connects Modbus RTU slave devices to IoT DC3: acting as the master, it reaches slaves on an
RS-485/RS-232 bus over a single serial port, periodically reads coil/register values, and supports commands that write
to coils and holding registers. By the end of this page you can configure the serial parameters, function codes, and
addresses for a serial Modbus device, and know where to look when it won't connect.
Protocol background
Modbus is an industrial protocol born in 1979 for serial PLC communication, and it remains one of the most common
protocols on the plant floor — heavily used by PLCs, energy meters, VFDs, temperature controllers, and sensors. Modbus
RTU is its serial-link variant: messages travel as compact binary frames over an RS-485/RS-232 bus, with a CRC to
guarantee integrity. It shares the exact same function codes and address model as
the Modbus TCP Driver — reads use 01/02/03/04, writes use 05/06/15/16, and addresses are 0-based
offsets — the only difference being the physical layer: RTU runs over a serial port (baud rate, data bits, parity, stop
bits) rather than IP/port.
In the four-layer IoT architecture, Modbus RTU sits at the network layer: it answers "what signaling and what rules
to exchange bytes over" between field devices and the polling master. It is a textbook master/slave request-response
protocol — the master polls slaves and waits for replies, slaves never speak unprompted; one RS-485 bus can carry
multiple slaves, distinguished by unit ID (slaveId). The protocol itself often just moves bytes, and how those bytes
are interpreted is decided by configuration (16-bit int vs 32-bit float, low byte first vs high byte first) — the most
common pitfall on the floor. For the general background on addressing, byte order, and the polling model,
see IoT network layer: Industrial Buses & Protocols.
- Driver name / code:
Modbus RTU Driver/ModbusRtuDriver - Type:
DRIVER_CLIENT(actively connects to slaves) - Underlying libraries: modbus4j + jSerialComm (one dedicated serial connection per device)
Attribute configuration
Modbus RTU configuration spans three layers: driver attributes (driver-attribute, device-level) describe how this
serial port is opened; point attributes (point-attribute) describe which slave and register each collected point
reads; command attributes (command-attribute) describe where a writable point writes. The defaults and
descriptions in the three tables below all come from the driver's application.yml; for where attributes originate
across the three layers, see Attributes & config.
Driver attributes (device-level driver-attribute)
When onboarding a Modbus RTU device, set these five serial parameters on the Device.
They are passed verbatim to jSerialComm's setComPortParameters to open the port, so they must match the slave's
serial settings one by one — unlike TCP, RTU has no handshake negotiation, and a mismatch just yields garbage or
timeouts:
| Attribute | code | Type | Default | Description |
|---|---|---|---|---|
| Port | port |
STRING | /dev/ttyUSB0 |
Serial port name (e.g. /dev/ttyUSB0, COM3) |
| Baud Rate | baudRate |
INT | 9600 |
Serial baud rate (e.g. 9600, 19200, 115200) |
| Data Bits | dataBits |
INT | 8 |
Data bits (7 or 8) |
| Stop Bits | stopBits |
INT | 1 |
Stop bits (1 or 2) |
| Parity | parity |
INT | 0 |
Parity (0=None, 1=Odd, 2=Even, 3=Mark, 4=Space) |
Point attributes (point-attribute)
Set three attributes on each collected Point, pinning down "which slave's which address, read with which function code":
| Attribute | code | Type | Default | Description |
|---|---|---|---|---|
| Slave ID | slaveId |
INT | 1 |
Modbus slave unit ID |
| Function Code | functionCode |
INT | 1 |
Read function code [1, 2, 3, 4] |
| Offset | offset |
INT | 0 |
Register/coil address offset (0-based) |
::: tip The function code decides what is read; the Point type decides how bytes are assembled
Reading supports four function codes: 01 (coil) / 02 (discrete input) / 03 (holding register) / 04 (input
register). For register reads (03/04), the driver uses the Point's data
type (Point's pointTypeFlag) to decide how many registers to take and how to
interpret them: LONG→4-byte signed int, FLOAT→4-byte float, DOUBLE→8-byte float, everything else 2-byte signed
int. Get the Point type wrong and a float reads back as a meaningless large number.
:::
Command attributes (command-attribute)
Writable Points also need four attributes on the write command. valueTemplate is the value template, rendered with
command params before the write is issued:
| Attribute | code | Type | Default | Description |
|---|---|---|---|---|
| Slave ID | slaveId |
INT | 1 |
Modbus slave unit ID |
| Function Code | functionCode |
INT | 6 |
Write function code (the driver actually handles only 1 write coil and 3 write holding register) |
| Offset | offset |
INT | 0 |
Register/coil address offset (0-based) |
| Value Template | valueTemplate |
STRING | ${value} |
Value template rendered with command params |
Collection & health
- Collection cycle: default cron
0/30 * * * * ?(reads all points once every 30 seconds). - Health / online: device health check default cron
0/15 * * * * ?, lease timeout45 seconds— the driver decides online/offline from whether the serial connection is initialized; see Device for the online-state mechanism.
The minimal onboarding path: create a Device with Modbus RTU Driver and set driver
attributes port=/dev/ttyUSB0, baudRate=9600, dataBits=8, stopBits=1, parity=0; on the
bound Profile, add a temperature Point (
pointTypeFlag=FLOAT, READ_ONLY) with point attributes slaveId=1, functionCode=3, offset=0; start the driver,
and within 30 seconds the collected value shows up in PointValue.
Troubleshooting
::: warning One wrong serial parameter and nothing connects
All five of port, baudRate, dataBits, stopBits, parity must match the slave's serial settings one by one. RTU
has no handshake negotiation, so any mismatch yields garbage or timeouts rather than a clear error. Confirm cabling and
baud rate with a multimeter / serial terminal first, then check parity (many meters default to even parity 2, not the
default no-parity 0).
:::
::: warning Three consecutive failures trigger a 60-second backoff; the device is offline throughout
The driver tracks consecutive failures per device: after 3 consecutive connection failures it enters a 60-second
backoff (FAILURE_BACKOFF_THRESHOLD=3, FAILURE_BACKOFF_MS=60000), during which the health check reports offline
outright and stops attempting connections. So even after you fix the serial parameters or cabling, you must wait out the
backoff before it reconnects — don't keep tweaking config inside the backoff window and conclude it "still won't
connect."
:::
::: warning offset is a 0-based protocol address, not 40001
offset is the protocol-level 0-based offset. To read "holding register 40001" in the conventional Modbus notation, set
functionCode=3, offset=0 (the 2nd holding register is offset=1, and so on). Putting 40001 straight into offset
reads the wrong address or goes out of range.
:::
::: warning Byte order: a 32-bit float read as a huge number usually means swapped register order
A 32-bit FLOAT/LONG spans two 16-bit registers, and field devices use one of four register orderings (
ABCD/CDAB/BADC/DCBA). This driver interprets registers in modbus4j's default order; if the float reads back as a
meaningless large number, the slave is most likely using the opposite register order — adjust the byte-order setting on
the slave side, or switch to an integer type and convert from the raw register value in an upper layer.
:::
::: tip Multiple slaves share one serial port, addressed by slaveId
An RS-485 bus can carry multiple slaves; they share the same port and are distinguished by the Point's slaveId. The
driver keeps one connection per Device ID (connectMap), so slaves on the same
physical bus should be created as devices pointing at the same port and addressed via slaveId — do not assign a
different serial port per slave. Note that a serial port is an exclusive resource: make sure that port is not held by
another process (and on Linux the running user needs read/write access to /dev/ttyUSB*).
:::
How it lands in IoT DC3
Whatever the underlying protocol, everything converges on the platform into a
single Point and its PointValue. The Modbus
RTU driver registers with dc3.driver.code = ModbusRtuDriver, the stable routing identifier the platform uses to
dispatch read/write commands to this driver.
Per the driver capability matrix, this driver's capabilities are:
| Capability | Supported | Implementation notes |
|---|---|---|
| Read | ✓ | Function codes 01/02/03/04, covering coils, discrete inputs, holding registers, input registers |
| Write | ✓ | Only 01 (write coil) and 03 (write holding register) |
| Subscribe | — | Master/slave polling protocol; no device-initiated reports, the collection cycle reads on a timer |
::: info Implementation status: available
ModbusRtuDriverCustomServiceImpl's read()/write()/health() and connection management are fully implemented (on
modbus4j + jSerialComm) — not a skeleton. The read path supports all four read function codes; connection handling,
backoff, health detection, and metadata events (destroying the stale connection when a device is updated or deleted) are
all in place.
:::
::: warning Write commands only support coils and holding registers
The command attribute functionCode defaults to 6, but write() actually handles only 01 (write coil) and 03 (
write holding register) — codes like 15/16 fall into the default branch and return false, so the write fails
silently. For writable Points, set functionCode=1 for coil writes and functionCode=3 for holding-register writes.
:::
Further reading
- Drivers overview — all protocol drivers and the entry point for selection
- Driver capability matrix — quick reference for read/write/subscribe per driver
- Device onboarding — a full onboarding walkthrough
- Industrial Buses & Protocols — network layer: addressing, byte order, and the polling model
- Modbus TCP Driver — the Ethernet flavor of Modbus, with the same function codes and address model