Melsec Driver
dc3-driver-melsec onboards Mitsubishi PLCs into IoT DC3 over the MC protocol: it acts as an MC client, actively
connects to the PLC, periodically reads by the device address configured on
each Point, and supports commands that write values back to devices. After reading
this page you can fill in the driver / point attributes, onboard a Mitsubishi PLC, and know where to look when it won't
connect.
Protocol background
The MC protocol (MELSEC Communication) is the native communication protocol of Mitsubishi Electric PLCs, widely used
across the A, QnA, Q/L, and iQ-R series. On the plant floor a Mitsubishi PLC exposes an MC server port through its
Ethernet module or built-in CPU port; an upstream system connects as an MC client and reads/writes data units in PLC
memory by their device address (e.g. D100, M0) — data registers hold process parameters, internal relays hold
logic state, input/output relays map to field IO.
In the four-layer IoT architecture the MC protocol sits on the wired-industrial side of the network layer: it is the "last mile" language contract between a PLC and upstream systems, governing how bytes are laid out, how devices are addressed, and the request-response timing of each exchange. Like Siemens S7 and Omron FINS, it is a vendor-proprietary master/slave protocol — the PLC never reports unprompted; the master must ask. To see where it sits in the protocol landscape and why PLC vendors' protocols are mutually incompatible, read IoT network layer: industrial buses and protocols.
The driver is built on the McPLC of the iot-communication protocol library, automatically selecting the matching
word width and codec by the point's data type when reading or writing.
- Driver name / code:
Mitsubishi Melsec Driver/MelsecDriver - Type:
DRIVER_CLIENT(actively connects to the PLC)
::: tip A few MC concepts first
Device (also called memory address): a data unit in a Mitsubishi PLC partitioned by purpose — e.g. D (data
register, the most common), M (internal relay), X (input relay), W (link register). Device address: a complete
address string made of an area prefix plus a number, e.g. D100, M0, X10, W200 — the area and number are written
together, not split into two fields. PLC Series: the MC frame format differs slightly between series, so choose
A / QnA / Q_L / IQ_R to match the actual PLC.
:::
Attribute configuration
Melsec driver configuration has two layers: driver attributes describe "which PLC to connect to" (device-level, one
set per device), and point attributes describe "which device to read" (point-level, one set per point). Both layers
are declared in the driver's application.yml; you fill the values in the console at onboarding time.
Driver attributes (device-level driver-attribute)
host / port decide which PLC's MC server port the TCP connection targets; series decides which framing the MC
frame uses and must match the real PLC series. When onboarding a Melsec PLC, fill
these Attributes on the Device:
| Attribute | code | Type | Default | Description |
|---|---|---|---|---|
| Host | host |
STRING | 192.168.0.20 |
PLC host address (Ip) |
| Port | port |
INT | 6000 |
MC service port |
| PLC Series | series |
STRING | QnA |
PLC series, A/QnA/Q_L/IQ_R |
Point attributes (point-attribute)
address specifies the device to read/write (whole-string notation, area + number written together); length is only
used for the string type — the byte length of the string to read. Fill these on
each Point:
| Attribute | code | Type | Default | Description |
|---|---|---|---|---|
| Device Address | address |
STRING | D100 |
Device address (D100, M0, X10, W200, etc.) |
| String Length | length |
INT | 0 |
String read length (0 for non-string types) |
::: tip The data type decides how many words to read and how to decode them
The driver picks the read/write width and codec automatically from the point's data
type (Point's pointTypeFlag): BOOLEAN reads/writes a bit, BYTE reads/writes 8
bits, SHORT reads/writes 16 bits (int16), INT/FLOAT read/write 32 bits, LONG/DOUBLE read/write 64 bits,
STRING reads/writes a string. Only the STRING type uses length (the number of bytes to read; the driver falls
back to 64 when it is 0 or empty); for non-string points keep length=0 and the driver ignores it.
:::
Write command: reuses the point address, no separate attribute
This driver supports writing values to a point (numeric, boolean, and string alike), but there is no
separate command-attribute — a write command reuses the address already configured on the point, the target device
is the point's address, and the word width of the written value is determined by the data type of the value being
issued. So a writable point needs no extra configuration; just mark the point as writable in
the Profile.
Acquisition and health scheduling
These crons come from the schedule / health sections of application.yml and govern the acquisition cadence and
online detection:
- Acquisition cycle: default cron
0/30 * * * * ?(one read round every 30 seconds). - Custom task: default cron
0/5 * * * * ?(the Melsec driver currently has no custom task;schedule()is an empty implementation and the schedule slot is reserved). - Health / online: device health check default cron
0/15 * * * * ?, lease timeout45 seconds— the driver judges online status by whether the TCP connection is alive; on a read/write exception it proactively disconnects and evicts that connection from the cache, and the next acquisition round reconnects automatically. See Device for the online-status mechanism.
Troubleshooting
::: warning Write address as the full device address — don't split area and number
Fill address with Mitsubishi's whole-string notation, e.g. D100, M0, X10, W200 — the area prefix and the
number go in the same string. This differs from protocols configured as "area + numeric offset" in two fields (such
as FINS); do not split the area and number into two entries, or McPLC parses an invalid address and the
read/write fails.
:::
::: warning series must match the real PLC series
series accepts only A / QnA / Q_L / IQ_R, which determines the MC frame format. A wrong or unrecognized value
makes the driver log Unknown series ... fallback to QnA and fall back to QnA — which may read incorrect data or
error outright on other-series PLCs. Confirm the series against the actual model before onboarding.
:::
::: warning When it won't connect / read-write fails, check the PLC-side MC service first
The driver opens a TCP connection directly to host:port; a failed connect throws Driver connection failed. Common
causes: the PLC Ethernet module has no MC service enabled, the port differs from port (many models do not default to
6000), PLC-side IP filtering or an exhausted connection limit, or a firewall block. Confirm the port is reachable with
telnet host port, then verify the MC service port and protocol (TCP) in the PLC project.
:::
::: warning If strings or byte order read back wrong, check the type and length
A garbled or truncated string usually means length does not match the PLC-side string byte count (with 0 left in, the
driver reads 64). An off numeric value usually means the point's pointTypeFlag does not match the word width actually
stored in the device — configuring a 32-bit float device as SHORT only reads the low 16 bits.
:::
::: tip One driver instance can serve multiple PLCs, with connections cached per device
A single Melsec driver process can serve multiple devices, each maintaining its own McPLC connection (cached by device
ID in connectMap) and serializing read/write with its own ReentrantLock. Multiple PLCs are distinguished by their
respective host. When a device is updated or deleted, the driver receives a metadata event and closes and evicts the
corresponding connection.
:::
How it lands in IoT DC3
::: info Implementation status: available
Both the read and write paths of the Melsec driver are fully implemented — read() / write() call real MC
reads/writes through iot-communication's McPLC (readInt16 / writeInt16 / readString, etc.), selecting the
correct word width by data type. This is an available driver, and its behavior matches the application.yml
declaration.
:::
- dc3.driver.code:
MelsecDriver— the driver's stable routing identifier inside the platform; device-to-driver binding and message dispatch address it by this code, so don't change it casually. - Read capability: ✓ supported. Reads periodically on the acquisition cycle, covering all of
BOOLEAN/BYTE/SHORT/INT/LONG/FLOAT/DOUBLE/STRING, consistent with MELSEC's "read ✓" in the driver capability matrix. - Write capability: ✓ supported. On a write command it writes the matching word width by the value's data type, consistent with the matrix's "write ✓".
- Subscribe capability: — not supported. MC is a master/slave polling model; this driver polls on the acquisition cycle and offers no PLC-pushed subscription, consistent with the matrix's "subscribe —".
Minimal onboarding example: onboard a QnA-series Mitsubishi PLC at IP 192.168.0.30:6000 and acquire a 16-bit
integer from D100:
- Create a Device using
Mitsubishi Melsec Driver, with driver attributeshost=192.168.0.30,port=6000,series=QnA. - Add a Point (
pointTypeFlag=SHORT,READ_ONLY) to the Profile bound to the device, with point attributesaddress=D100,length=0. - Start the driver, and within 30 seconds the acquired value of
D100appears in PointValue.
For the full onboarding flow (modeling, binding, dispatch) see Device onboarding.
Further reading
- Driver overview — entry point to all drivers and their categories
- Driver capability matrix — a quick read/write/subscribe lookup per driver
- Device onboarding — a complete onboarding walkthrough
- Industrial buses and protocols — where the MC protocol sits in the network-layer protocol landscape
- FINS Driver — a TCP industrial protocol for Omron PLCs, addressed by "area + offset" in two fields