title
title
FINS Driver

FINS Driver

dc3-driver-fins onboards Omron PLCs into IoT DC3 over the FINS protocol: as a FINS client it actively opens a TCP connection to the PLC, periodically reads values by the memory area and word address configured on each Point, and supports commands that write values back to memory areas. By the end of this page you can onboard an Omron PLC and know exactly how far the current implementation goes.

  • Driver name / code: Omron FINS Driver / FinsDriver
  • Type: DRIVER_CLIENT (actively connects to the PLC)

Protocol background

FINS (Factory Interface Network Service) is the native communication protocol of Omron PLCs, widely used across the CP/CJ/CS series. It partitions PLC memory by purpose into several Memory Areas, each addressed in units of one " word" (16 bits); a host accesses data by sending memory read/write command frames carrying a memory-area code plus a word address. FINS can run over UDP, TCP, Ethernet, or Omron's proprietary buses; this driver uses FINS/TCP, prepending a 4-byte length prefix to each FINS frame.

In the four-layer IoT architecture, FINS sits at the network layer: it defines how devices on the shop floor are addressed, how commands are encoded, and how bytes travel on the link. IoT DC3 normalizes on top of it, translating "read the word at D100" into a uniform PointValue.

::: tip A few FINS concepts first Memory Area: a region of PLC data partitioned by purpose——D (data memory, the most common), W (work), H ( holding), C (counter). This driver maps them to FINS area codes: D=0x82, W=0xB1, H=0xB0, C=0x83. Word Address: an offset within a memory area in units of one "word" (16 bits), e.g. D100 is the 100th word of the D area. Node/Unit number: the source/destination addresses used to reach a PLC on the FINS network; for a single direct connection these usually stay at their defaults. :::

How one FINS read frame is assembled

The driver uses no third-party protocol library; it assembles FINS frames byte by byte. A request to read 1 word consists of a 4-byte TCP length prefix + a 10-byte FINS header + a 2-byte command code + 4 bytes of read parameters:

flowchart LR
  subgraph TCP["FINS/TCP frame"]
    Len["TCP length prefix<br/>4 bytes"]
    subgraph FINS["FINS frame"]
      Hdr["FINS header 10 bytes (driver implementation)<br/>ICF 0x80 / RSV / GCT 0x02<br/>destNode destUnit 0x00 / srcNode srcUnit 0x00 / SID"]
      Cmd["command code 2 bytes<br/>MRC 0x01 / SRC 0x01 (memory read)"]
      Par["read params 4 bytes<br/>area code + word address + bit + length"]
    end
  end
  Len --> Hdr --> Cmd --> Par

The response frame carries a 2-byte end code after the FINS header and command code: non-zero means the PLC rejected or errored, and the driver raises a ReadPointException accordingly; when it is zero, data starts at byte 14 and is decoded per dataType (see the implementation-status note below).

Attribute configuration

FINS onboarding parameters fall into two groups: which PLC to connect to is set by device-level driver attributes; which word each point reads/writes is set by point/command attributes. The fields in the three tables below all come from the driver's application.yml, and the prose before each table explains what every attribute does and where its value comes from.

Driver configuration (device-level driver-attribute)

When onboarding a FINS PLC, fill these Attributes on the Device. host/port point at the PLC; sourceNode/destNode/sourceUnit/ destUnit are the source/destination addressing bytes in the FINS header, fine at their defaults for a single direct connection; timeout serves as both the TCP connect timeout and the read timeout (setSoTimeout).

Attribute code Type Default Description
Host host STRING 127.0.0.1 PLC host address
Port port INT 9600 FINS port (standard 9600)
Protocol protocol STRING TCP Transport protocol (the driver always uses FINS/TCP)
Source Node sourceNode INT 1 FINS source node number
Dest Node destNode INT 2 FINS destination node number
Source Unit sourceUnit INT 0 FINS source unit number
Dest Unit destUnit INT 0 FINS destination unit number
Timeout timeout INT 5000 Connect / request timeout (milliseconds)

Point configuration (point-attribute)

Fill the read target on each acquisition Point. memoryArea + address together locate one word (e.g. memoryArea=D, address=100 corresponds to Omron's familiar D100); dataType declares the decoding; bitPosition is the bit offset within the word.

Attribute code Type Default Description
Memory Area memoryArea STRING D Memory area, D/W/H/C
Address address INT 0 Word address within the memory area
Data Type dataType STRING UINT16 INT16/UINT16/INT32/UINT32/FLOAT/STRING/BCD
Bit Position bitPosition INT 0 Bit offset within the word (unused on the current read path; treated as 0)

::: warning The current read path reads exactly 1 word; dataType does not decide how many words are read A read always fetches exactly 1 word (2 bytes), regardless of dataType. So only INT16/UINT16 read back correctly; for INT32/UINT32/FLOAT, decodeValue calls getInt()/getFloat() to read 4 bytes from a 2-byte buffer, triggering a BufferUnderflow, so no value is produced today; STRING/BCD likewise only receive 2 bytes. These are declared but pending protocol semantics. The driver decodes the returned bytes Big-Endian; the Point's data type (Point's pointTypeFlag) should match the dataType set here. :::

Write command configuration (command-attribute)

Writable points additionally need the target location and write type on the write command; the field meanings are the same as in the point configuration.

Attribute code Type Default Description
Memory Area memoryArea STRING D Memory area, D/W/H/C
Address address INT 0 Word address within the memory area
Data Type dataType STRING UINT16 Data type of the written value

Acquisition and health scheduling

These cadences are fixed in the schedule/health sections of application.yml; you do not re-enter them on the device:

  • Acquisition cycle: default cron 0/30 * * * * ? (reads once every 30 seconds).
  • Custom task: default cron 0/5 * * * * ?, but the FINS driver's schedule() is an empty implementation——the slot is reserved and currently does nothing.
  • Health / online: the device health check defaults to cron 0/15 * * * * ? with a lease timeout of 45 seconds. The driver decides online status by whether the TCP connection is alive ( socket.isConnected() && !socket.isClosed()); a dropped connection triggers a reconnect attempt, and a failed reconnect marks the device offline. For the online state mechanism see Device.

Troubleshooting

::: warning address is a word address, not a region-prefixed string address takes only the numeric offset within the memory area. To read Omron's familiar D100, set memoryArea=D and address=100——do not put D100 as a whole into address. The area is specified separately by memoryArea. memoryArea only recognizes D/W/H/C; any other value is silently treated as D (0x82). :::

  • Cannot connect / stuck offline: first confirm the PLC has FINS/TCP enabled on port 9600 (the driver is TCP-only and does not fall back to UDP). On a failed connection the driver logs Driver FINS connection failed and marks the device offline, retrying on the next health-check cycle. Check host, network reachability, and whether the PLC limits the number of client connections.
  • Wrong value / BufferUnderflow: usually dataType is set to INT32/UINT32/FLOAT/STRING/BCD——the current read path takes only 1 word (2 bytes), so only INT16/UINT16 work. Multi-word types are pending implementation; validate the link with a 16-bit type first.
  • Non-zero endCode: bytes 12–13 of the response frame are the FINS end code; non-zero means the PLC rejected the request (e.g. address out of range, memory area absent, insufficient permission). The driver throws FINS command failed, endCode=0x...; look the code up in the FINS manual and verify memoryArea/address fall within the PLC's actual memory range.
  • Float writes land wrong: the write command parses INT32/UINT32/FLOAT all via Integer.parseInt before writing 4 big-endian bytes, and does not encode 12.5 as a float. To write a float, convert the target to its integer bit pattern yourself, or confirm the PLC actually expects an integer.
  • Frequent timeouts: timeout governs both connect and read (default 5000ms). Increase it for a jittery link or a slow PLC; note that any read/write exception actively closes and evicts that device's cached connection, which is rebuilt on next access.
  • Node addressing fails: FINS scenarios crossing gateways/routers need correct sourceNode/destNode. Note the current implementation: after GCT the driver writes destNode/destUnit and srcNode/srcUnit directly, and does not emit separate zeroed DNA/SNA network-address bytes——the header does not strictly distinguish network addresses from node numbers (the node number occupies the DNA/SNA slots from the spec). A single direct connection works with the defaults 1/2; across gateways and multi-level routing this simplified header may address incorrectly.

How It Lands in IoT DC3

  • dc3.driver.code: FinsDriver (stable routing identifier used for registration and command dispatch; do not change it casually).
  • Read capability: ✓ implemented——periodic single-word polling, INT16/UINT16 work.
  • Write capability: ✓ implemented——INT16/UINT16/STRING write correctly; 32-bit/float are encoded as integers ( see Troubleshooting above).
  • Subscribe/report capability: — not provided. FINS is active-poll only; the driver does not listen for device pushes, consistent with the Driver Capability Matrix.

::: warning Multi-word data types are not yet implemented The read path always reads exactly 1 word; the INT32/UINT32/FLOAT/STRING/BCD decode branches are written but cannot produce correct values because only 2 bytes are fetched, and the write path encodes 32-bit/float as integers. The usable range today is 16-bit integers (plus STRING writes); multi-word types are designed but pending, so do not treat them as supported. :::

::: tip One driver instance can serve multiple PLCs A single FINS driver process can serve multiple devices, each holding its own TCP connection (cached by device ID in clientMap). Multiple PLCs are distinguished by their own host and destNode; when a device is deleted or updated, the driver destroys the matching connection via a metadata event. :::

Minimal onboarding example

Onboard an Omron PLC at IP 192.168.1.20:9600 and acquire one 16-bit integer at D100:

  1. Create a Device with Omron FINS Driver, set driver attributes host=192.168.1.20 and port=9600, and leave the rest (protocol, node/unit numbers, timeout) at their defaults.
  2. Add a Point (pointTypeFlag=INT, READ_ONLY) to the Profile bound to the device, with point attributes memoryArea=D, address=100, dataType=INT16.
  3. Start the driver; within 30 seconds the D100 value appears in PointValue.